CAPTIN 300FA

CAPTIN 300FA 300W/48DC fan cooled based solutions Site energy and management solution
CAPTIN 300FA 300W/48DC fan cooled based solutions Site energy and management solution

Site energy and management solution

  • High efficiency, 300W rectifier based solution
  • Full front access 1RU shelf
  • Wide AC input range
  • Integrated distribution
  • Battery backup connections and management
  • Multiple monitoring options
  •  Optional A + B feed (Dual AC input)

The CAPTIN 300FAR series is a highly modular solution based on the high efficient rectifier Cordex HP 48-300W, designed to power small loads at operating efficiency of 94%, a world class performance for 300W rectifiers. Designed to support uninterrupted operations 24/7, such efficiency brings significant savings in thermal management and operating expenses and reduces carbon footprint.

1RU high and 250mm deep, the system can accommodate up to three rectifiers, an embedded output distribution (standard or custom configured) including a managed battery connection, an energy controller and a site and access management module.  All elements are modular to optimize your solution and meet your needs and budget.    

Like all CAPTIN series solutions from Alpha Innovations, the CAPTIN 300FAR offers the opportunity to monitor and control an almost infinite number of operating parameters over TCP/IP.  The solution is based on Compas, a fully open platform compliant with the ETSI standards, and supports XML, SNMP and Web based services.  It is very easy to integrate in network applications and facilitates large savings in maintenance and intervention costs. For those looking for the lowest initial investment, the basic monitoring will report all major alarms on configurable standard dry loops.

Enjoy a fully hot pluggable modular solution, configured and fully tested to your needs, that is of course easily scalable at any time. Standard systems are delivered with one input connection; A+B feed configuration is optional.

The system offers full front access for any module, battery and DC loads connection or servicing and can be quickly installed and connected.

This solution can be configured to support NiMh batteries from ARTS Energy.

 

Electrical
Input Voltage:
90 to 265VAC
Input Frequency:
47 to 63Hz
Input Current:
10A max IEC on rear side (option:
pigtail)
Efficiency:
up to 94.5% (CXRFC48-300W)
Output voltage:
-40.5 to -58 58Vdc (0V conn. To Protect. Earth)
Power output:
900W max (3x300W)
Outputs load current (GMT fuses):
4x15A max (configurable)
Battery Current (breaker):
1x20A
Features
LVD circuit + Reverse polarity protection
 
Auxiliary Output 12V-1A:
with SAM0348
Alarms:
4 digital outputs (realays - NO/NC)
4 free digitals inputs on rear side
 
Optionnal front access for inputs/outputs.
 
Compatible with NiMH (option)
 
Mechanical
Dimensions:
 
mm:
43H (1U) x 440W x 250D
inches:
1.75H x 17.3W x 9.45D
Mounting:
19" or ETSI
Weight:
 
Shelf:
2kg (4.41lb)
Rectifier:
0.57kg (1.23lb)
Connections
 
Load distribution (GMT fuses):
 
4 Positions:
Spring cage terminal block (0.2 to 2.5mm²)
Battery (breaker):
Female 2 poles connector (0.2 to 4mm²)
AC Input:
 
Standard:
IEC C16 plug connector
Optional:
3 x 2.5mm² pigtail (2m single cord)
Alarms:
 
Rear side:
Female 3 x 8 poles connectors
Standard I/O card (Optional):
Female Sub D26
Standard I/O card (Optional):
see specificications sheet
Environmental
Temperature:
 
Standard:
-20 to 70°C (-4 to 158°F)
Extended (derated output power):
-40 to 70°C (-40 to 158°F)
Storage:
-40 to 85°C (-40 to 185°F)
Humidity:
 
Operating:
20 to 80% RH non-condensing
Storage:
10 to 95% RH non-condensing
Elevation:
Up to 3000m (9842ft)
Cooling:
Fan cooled (front to rear)
Standards
Safety:
CE marked
 
EN60950-1 (CEBEC-SGS marked)
Insulation:
Input-Output:
4242Vdc; Input-Earth:
min 2121Vdc
Environment:
RoHS compliant
EMC:
see module CXRF-300W
Immunity:
EN61000-4-3 (radiated immunity)
 
EN61000-4.2 (ESD)
 
EN61000-4-6 (conducted immunity)
 
EN61000-4-4 (Burst)
 
EN61000-4-5 (Surge immunity)
 
EN61000-4-11 (Voltage Dips and interrupts)
Emission:
EN55022 (conducted level B)
 
EN55022 (radiated level B)
 
EN61000-3-2 (Harmonic current) 
 
EN61000-3-3 (Voltage fluctuations and flicker)  

Standard Part Numbers
  • 9400 015 00051: CAPTIN300FA STD1 MCU PRO 0.5U SAM READY
  • 9400 015 00052: CAPTIN300FA STD2 MCU PRO LCD
Related Items
  • Connectors & cables:
  • Distribution:
    • DIST300B1O4: Distribution front access for CAPTIN300FA including battery connection with LVD protected by breaker and four outputs protected by fuses (values to be selected separately
  • Filler:
  • Fuses:
  • Mechanical:
    • 5304 500 01151: KIT PLEXI BACK WIRING CAPTIN300FA (to close rear DC access if required: systems not installed in enclosures)
  • Monitoring & Control:
    • ADIO DIN 17: Extension Module for measuring 10 temperatures (NTC)
    • MCU0348M4: 1U high controller for CAPTIN300 with LCD - no comp@s
    • MCU0348M4LP: 0,5U high controller for CAPTIN300 no LCD - no comp@s
    • STDIO CAPTIN300FA: I/O board for front connection of signals includes digital input connections on SUB-D, CAN port and temperature sensor connection
  • Sensors & Actuators:
    • 5304 500 00791: Temperature Sensor 3m long pigtail
    • 5304 500 00921: Temperature probe battery 1,54m with socket to fit in the distribution module or I/O board, ring tongue sensor M6
    • 5304 500 01141: Temperature probe 1,5m with bare wires (connection at the rear), ring tongue M5
  • Solution: