CAPTIN 300FAR

CAPTIN 300FAR 300W/48DC fan cooled based solutions Site energy and management solution
CAPTIN 300FAR 300W/48DC fan cooled based solutions Site energy and management solution

Site energy and management solution

  • High efficiency, 300W rectifier based solution
  • Full front access 1RU shelf
  • Wide AC input range
  • Integrated distribution
  • Battery backup connections and management
  • Multiple monitoring options
  •  Optional A + B feed (Dual AC input)

The CAPTIN 300FAR series is a highly modular solution based on the high efficient rectifier Cordex HP 48-300W, designed to power small loads at operating efficiency of 94%, a world class performance for 300W rectifiers. Designed to support uninterrupted operations 24/7, such efficiency brings significant savings in thermal management and operating expenses and reduces carbon footprint.

1RU high and 250mm deep, the system can accommodate up to three rectifiers, an embedded output distribution (standard or custom configured) including a managed battery connection, an energy controller and a site and access management module.  All elements are modular to optimize your solution and meet your needs and budget.    

Like all CAPTIN series solutions from Alpha Technologies, the CAPTIN 300FAR offers the opportunity to monitor and control an almost infinite number of operating parameters over TCP/IP.  The solution is based on Comp@s, a fully open platform compliant with the ETSI standards, and supports XML, SNMP and Web based services.  It is very easy to integrate in network applications and facilitates large savings in maintenance and intervention costs. For those looking for the lowest initial investment, the basic monitoring will report all major alarms on configurable standard dry loops.

Enjoy a fully hot pluggable modular solution, configured and fully tested to your needs, that is of course easily scalable at any time. Standard systems are delivered with one input connection; A+B feed configuration is optional.

The system offers full front access for any module, battery and DC loads connection or servicing and can be quickly installed

and connected.

 

Electrical
Input Voltage:
90 to 265VAC
Input Frequency:
47 to 63Hz
Input Current (per module):
1.40A @ 230Vac
 
3A @ 110Vac
 
3.7A @ 90Vac
Efficiency:
93.8% typical @ 230Vac
Output voltage:
43 to 58Vdc
Power output (Constant output power):
 
per module:
300W
maximum:
1200W
Current output
 
per module:
5.6A @ -54Vdc /  6.7A @ -45Vdc
maximum:
32A
Environment
Temperature:
 
Standard:
-20 to 70°C (-4 to 158°F)
Extended (derated output power):
-40 to 70°C (-40 to 158°F)
Storage:
-40 to 85°C (-40 to 185°F)
Humidity:
 
Operating:
20 to 80% RH non-condensing
Storage:
10 to 95% RH non-condensing
Elevation:
Up to 3000m (9842ft)
Cooling:
Fan cooled (front to rear)
Mechanical
Dimensions:
 
mm:
43H (1U) x 440W x 250D
inches:
1.75H x 17.3W x 9.45D
Mounting:
19" or ETSI
Weight:
 
Shelf:
2kg (4.41lb)
Rectifier:
0.57kg (1.23lb)
Connections
 
Load distribution (GMT fuses):
 
4 Positions:
Spring cage terminal block (0.2 to 2.5mm²)
Battery (breaker):
Female 2 poles connector (0.2 to 4mm²)
AC Input:
 
Standard:
IEC C16 plug connector
Optional:
3 x 2.5mm² pigtail (2m single cord)
Alarms:
 
Rear side:
Female 3 x 8 poles connectors
Standard I/O card (Optional):
Female Sub D26
Standard I/O card (Optional):
see specificications sheet
Standards
Safety:
CE marked
 
EN60950
Environment:
RoHS compliant
 
IEC 60068-2-27
 
ETSI EN 300 019-1-3 class 3.4
EMC:
ETSI EN 300386

Related Components
  • Connectors & cables:
  • Distribution:
    • DIST300B1O4: Distribution front access for CAPTIN300FA including battery connection with LVD protected by breaker and four outputs protected by fuses (values to be selected separately
  • Filler:
  • Fuses:
  • Mechanical:
    • 5304 500 01151: KIT PLEXI BACK WIRING CAPTIN300FA (to close rear DC access if required: systems not installed in enclosures)
  • Monitoring & Control:
    • 300W STI/O BOARD: I/O board for front connection of signals includes digital input connections on SUB-D, CAN port and temperature sensor connection
    • Compas 300W: Comp@s card including basic and battery software package
    • MCU0348M4: 1U high controller for CAPTIN300 with LCD - no comp@s
    • MCU0348M4LP: 0,5U high controller for CAPTIN300 no LCD - no comp@s
  • Rectifier Module:
  • Sensors & Actuators:
    • 5304 500 00791: Temperature Sensor 3m long pigtail
    • 5304 500 00921: Temperature probe battery 1,54m with socket to fit in the distribution module or I/O board, ring tongue sensor M6
    • 5304 500 01141: Temperature probe 1,5m with bare wires (connection at the rear), ring tongue M5
  • Shelf:
    • 4004 120 00421: EMPTY SHELF CAPTIN300FA 4 RECT 1 IEC320 MAINS
    • 4004 120 00431: EMPTY SHELF CAPTIN300FA 3 RECT 1 IEC320 MAINS
    • 4004 120 00441: EMPTY SHELF CAPTIN300FA 4 RECT 2 IEC320 MAINS
  • Solution: