CES48_01.png
Back to product finder
Remote Power Feeding - Up Converter

CES48

Remote Feeding Central Up Converter
Contact us

Summary

  • RFT-C operation mode
  • Up to 52 output lines
  • Full front access
  • Redundant DC input
  • 900W output power capability
  • Start-up protection system
  • Modular, hot pluggable module

Description

The Central Energy System is a solution to feed remote locations from a power source located in a central location (hub) over existing or new copper networks installed with the regulatory constraints applicable to telecom networks. The design based on the IEC (EN/UL) 60950/21 features the installation of 52 insulated and independent DC/DC  converters. The system can be connected to 48V or 60V redundant sources to provide superior availability of the services at remote locations.
 
The standard supports two modes for power transmission: RFT-C and RFT-V. The CES48/xxL320 is designed around the RFT-C mode to offer full safety in any conditions of operation and distance from the central office equipment. Furthermore, the RFT-C mode is easy to dimension and implement. The current limitation avoids potential overheating of cables.
 
The remote feeding solution from Alpha Innovations results from years of experience and work with leading network operators. Beyond the requirements of the standard, each line is protected to bring the maximum current capability well below the safety limits in case of short circuits line to line or line to ground. Feeding power at 320V in normal operation, the voltage of each line will go independently below 50V if the line is opened.
 
Remote feeding solution offers numerous advantages versus traditional AC/DC conversion for remote locations. If the most obvious advantage is to support high availability of signals while avoiding the multiplication of batteries in the field, it also eases and supports faster network deployment. In many applications it finally brings significant measurable cost savings compared to traditional solutions.
 
The system is designed primarily to be installed in central office equipment, but can also be installed as one component of a delocalized power hub serving multiple small remote nodes. Designed and manufactured with state-of-the-art technologies and processes, electronic cards are hot pluggable and very easy to install and replace without any specific tools or special care.
 

Datasheet

Electrical

  • Input Voltage: -39.6 to -72Vdc
  • Input Current 
    • per module: 2.2A@39.6Vdc - 1.62@54Vdc
    • Full 14 cards system: 31A@39,6Vdc - 19A@54Vdc
  • Number of input: 2 (protected by breakers)
  • Efficiency: 85% typical @54Vdc (including start-up protection system)
  • Power output: 
    • per line: 18.6W
    • Full 14 cards system: 890W
  • Current output: 
    • per line: 58mA @ 320Vdc
    • Full 14 cards system: 2.78A @ 320Vdc

Mechanical

  • Dimensions: 
    • mm: 183H x 448W x 250D
    • inches: 7,2H x 17,6W x 9,4D
  • Mounting: 19" or ETSI (Additional brackets)
  • Weight: 
    • Empty shelf: 4.1kg (9.04lb)
    • Up converter module: 0.23kg (0.51lb)
  • Connections
    • DC output (4 Positions): Female 8 poles connector
    • DC Input: Female 2 poles connector (Molex Mini-Fit)
    • Alarms: Female 3 poles connector (Mate-N-Lok)

Environmental

  • Temperature: 
    • Standard: -5 to 45°C (23 to 113°F)
    • Storage: -40 to 85°C (-40 to 185°F)
  • Humidity: 
    • Operating: 5 to 95% RH non-condensing
    • Storage: 5 to 100% RH non-condensing
  • Elevation: Up to 2500m (8200ft)
  • Cooling: Fan cooled (with fan tray)

Standards

  • Safety: 
    • CE marked
    • EN60950
  • Environment: 
    • RoHS compliant
    • IEC 60068-2-27
  • EMC: ETSI EN 300 386

Standard Part Numbers

9400 011 XXX

Related Items

  • Accessories - Connectors And Cables
  • 5304 500 01391Mating connector 8p, 3,5mm, STR, FEM
  • 5304 500 00721Mating power connector 8p, 3,50mm 8A (Multiple = 50p)
  • 5304 500 00731KIT WCS CENTRAL 2 inputs with 4 m pigtail cables and 1 alarm with pigtail cable 3 m.
  • 5304 500 00961Mating con 2p for monitor COM or CAN (Qty=50)
  • 4004 003 87641CON,PLUG,8P,3.50mm,8A,160V,SCREW CON (for output or monitor COM)
  • 5304 500 00861Mating connector kit for 60W down converter
  • 5304 500 00871Mating connector kit for controller REM06L3MOD
  • 5304 500 01561Mating connector kit for 120W down converter
  • 5304 500 00901Output power connector for 60W and 120W down converters (box of 50 pieces)
  • 5304 500 35001CES48 - Assembled cable kit (28 pairs cable with mating connectors for 7 cards)
  • 5304 500 36001CES48 - Alarm Cable
  • Accessories - Filler
  • 5304 500 00711BLIND PANEL 3U CENTRAL (Qty=10)
  • 4004 117 81291CES48 - Blind Panel For Central Unit
  • Accessories - Mechanical
  • 5304 500 00691CES48 - Mounting Brackets for ETSI frame
  • 4004 117 86711DECORATIVE PANEL BETWEEN 2 SUB-RACKS
  • Accessories - Fan Tray
  • CO4489/50Rear Fan Tray
  • CO4489/51Fan Control Card
  • CO4489/53Front Fan Tray
  • Monitoring and Control - Remote Feeding
  • CEM03CController for up to four remote sites.
  • MCU-CES48Control Card with comp@s card for monitoring over TCP/IP. Can monitor up to 256 Sites
  • Remote Power Feeding - Up Converter
  • CEC4L350WGACRLP UP-CONV 48V/350V K20 COMPLIANT CEC4L350WGAC (Coated)
  • Remote Power Feeding - Down Converter
  • REC010D48FNRLP 120W down converter with integrated monitoring
  • Remote Power Feeding - Splitter
  • RLP Splitter Module1U Splitter RLP for DSL
  • RLP Splitter ShelfSubrack for up to 4 RLP DSL splitter module

Search for tailor-made solution ?

Contact us
We use cookies to provide a better experience. By continuing to use the site you accept this policy. Learn more