The MCU0x48* is a microcontroller-based monitoring system intended for use in telecommunication power plants using the 300W and 1000W rectifiers. It allows monitoring and controlling of up to 4 rectifiers (10 with Comp@s platform), one battery string and a power distribution in a 1-3U power shelf (depending of the number of rectifier).
The controller is a hot-pluggable, hot-swappable unit that fits into 1U height, alongside the rectifier modules. The MCU0x48 is Comp@s platform ready, allowing advanced monitoring trough Ethernet/USB. Moreover, it allows interoperability with peripherals/equipments connected on the CAN bus (Cabinet security and environmental management)
Datasheet
- Communication Interface :
- Ethernet 10/100 Mbit
- USB
- CAN
- 4 Relays : max 60VDC (42VAC)
- Digital Inputs : TTL compatible, with integrated pull-up resistors of 100kohm.
- Controller I/O :
- Dc Bus Voltage
- Battery Current
- Battery Temperature
- Rectifier Status
- Digital Inputs
- 4 potenial free relays (NO/NC)
- Battery Management :
- Current Limitation
- Temperature Compensation
- Battery test
- Capacity Estimation
- …
- Temperature :
- Operation : -40 to 70°C
- Humidity :
- Operating:20 to 80% RH non-condensing
- Operating Optional :up to 95% with optional coating
- Storage:10 to 95% RH non-condensing
- CE marked
- CEBEC markings
- IEC 62368-1
- IEC 62368-3 (USB power)
- EMC inside shelf * (Residential and Insustrial levels) :
- EN 61000-6-1 / ETSI EN300386
- EN 61000-6-3
- * See specifications sheet for more details
- Environment : RoHS compliant
- 9413 060 10161 : MCU0x48M4 1U WITH OLED Screen