CAR30100TP-A_01.png
Back to product finder
DC Power - Rectifiers

CAR30100TP-A

Contact us

Summary

  • Improved robustness regards to CAR30100TP
  • Fans block in front can be replaced (preventive maintenance)
  • Operating from -40°C to 70°C
  • Universal wide AC input
  • Wide DC input up to 402Vdc
  • Basic shelf: ACE306
  • 3kW (Up to 18kW output power in 3U high shelf)

Description

The CAR30100TP-A (3kW) can be used for industrial and railways applications. It can be integrated in a shelf which can supply up to 18kW under voltage from 80 up to 115V. It creates a wide range of opportunities for highly reliable controls of costs in energy consumption, load management, environmental operating conditions, inventory management, site maintenance and intervention. Besides its robustness, fan blocks can be easily replaced for preventive maintenance.   

Datasheet

Electrical

  • Input Voltage:
    • Standard AC: 100 to 240Vac (+-10%)
    • Standard DC: 100 to 330Vdc (-15%  +20%)
    • Maximum: 300Vac - 410Vdc (without damages)
  • Input Frequency: 47 to 63Hz
  • Power factor: 0.99%
  • Input Current:
    • 14A @ 230Vac
    • 18.5A @ 110Vac
    • 22A max (AC or DC input mode)
  • Efficiency: 93% typical
  • Output voltage: 80 to 115 Vdc
    •  Product option for 84V and 96V, contact rfq@alphainnovations.eu
  • Output power:   
    • 3000W from 180Vac to 265Vac input
    • 1800W from 100Vac to 132Vac input (1600W at 90Vac)
    • 1575W to 3000W from 85Vdc to 180Vdc input
    • 3000W from 180Vdc to 402Vdc input
  • Output current:  
    • 27.5A @ 109Vdc High mains
    • 16.5A @ 109Vdc Low mains
  • Load regulation: ±0.5%
  • Line regulation: ±0.2%
  • Wide band noise: 20mVrms

Features

  • Protections:
    • Mains out of range
    • Output overvoltage and overload
    • Short circuit current
    • Smart power derating
    • Thermal shutdown
    • Hot swap

Mechanical

  • Dimensions: 
    • mm: 128H (3U) x 69W x 355D
    • inches: 5H x 2.7W x 14D
  • Weight: 3.5kg

Environmental

  • Temperature: 
    • Standard: -20 to 55°C
    • Extended: -40 to 70°C
    • Storage: -40 to 85°C
  • Humidity: 
    • Operating: 20 to 80% RH non-condensing
    • Storage: 10 to 95% RH non-condensing
  • Elevation: Up to 3000m
  • Cooling: Fan cooled (front to rear)

Standards

  • Safety:
    • CE marked
    • EN 62368-1
    • IEC 62368-1 (formerly IEC 60950-1) (CB with US and CAN deviations included)
    • CEBEC marking (c-SGS-us marking on request)
  • EMC* (Industrial levels and Railways environment): 
    • EN 61000-6-1
    • EN 61000-6-3
    • EN50121-4
  • * See specifications sheet for more details
  • Environment:
    • RoHS compliant

Standard Part Numbers

9411 013 08001

Related Items

  • DC Power - Basic Shelves
  • ACE306110Vdc 18kW Energy System

Search for tailor-made solution ?

Contact us